SECTION 10615
RELOCATABLE PARTITIONS
******************************************************************************
Use this guide specification to specify the ULTRAWALL
Partition Systems by USG Interiors, Inc. Obtain
copies of USG Publication SA-1020 and Technical Information
Guide MP-517 before editing specification.
The versatile ULTRAWALL system includes many optional
components and performance levels; edit Section
carefully to avoid conflicting requirements.
******************************************************************************
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Partition framing system.
B. [Prefinished] gypsum panels.
C. [Partition insulation] [and] [acoustical sealant].
D. Frames for [doors] [and] [glazing].
E. Trim and accessories.
******************************************************************************
Doors, glass, and hardware are usually be specified
in Division 8 but can be included in this Section if
appropriate.
******************************************************************************
F. [Doors,] [glass,] [and] [hardware] installed
in partition.
1.02 RELATED SECTIONS
******************************************************************************
Include sections specifying work effecting relocatable
partitions. Edit list according to Project
requirements.
******************************************************************************
A. Section 08100 - Metal Doors: Doors[.] [and fire-rated
frames.]
B. Section 08200 - [Wood] [and] [Plastic] Doors.
C. Section 08700 - Hardware: Finish hardware for
doors.
D. Section 08800 - Glass and Glazing.
E. [Section 09250 - Gypsum Board Systems: Non-relocatable
partitions.]
******************************************************************************
Retain below if resilient base is used instead of
standard ULTRAWALL base.
******************************************************************************
F. Section [09650 - Resilient Flooring:] [09680
- Carpet:] Resilient base.
G. [Section 09900 - Painting: Field painting of
unfinished partitions.]
H. [Section 09950 - Wall Coverings: Site installed
wall covering.]
I. Division 16 - Electrical: Electrical [and telephone]
wiring and devices within and on
relocatable partitions.
J. [________ - ________________________.]
1.03 REFERENCES
******************************************************************************
List only references that are included within the
text of Section.
******************************************************************************
A. AA - Aluminum Association.
B. ASTM C36 - Gypsum Wallboard.
C. ASTM C960 - Predecorated Gypsum Board.
D. ASTM E72 - Conducting Strength Tests of Panels
for Building Construction.
E. ASTM E84 - Surface Burning Characteristics of
Building Materials.
F. ASTM E90 - Method for Laboratory Measurement
of Airborne Sound Transmission Loss of Building
Partitions.
G. ASTM E119 - Fire Tests of Building Materials.
H. ASTM E413 - Determination of Sound Transmission
Class.
I. FS CC-W-408A - Wall Covering-Vinyl Coated
J. FS HH-I-521 - Insulation Blankets, Thermal (Mineral
Fiber, for Ambient Temperatures).
K. UL - Underwriter's Laboratories, Inc. Fire Resistance
Directory.
L. WHI - Wernock Hersey International Certification
Listings.
M. Federal Test Method Standard No. 406, Method
1074.
1.04 SYSTEM DESCRIPTION
******************************************************************************
Partition is 3-3/8 inches wide, except two-hour fire
resistance-rated partition is 4-1/2 inches wide.
******************************************************************************
A. Partition system shall have components which
can be disassembled, relocated, and substantially
reused. System shall consist of vertical gypsum
board panels, floor runner, top rail, splice
studs, trim, and
accessories. Partition shall be [3-3/8] [4-1/2]
inches thick and provide 1-7/8 inches wide
cavity for distribution of utilities.
******************************************************************************
If including performance specifications, edit Section
carefully to avoid conflict between descriptive and
performance requirements. Refer to USG product literature
and test reports for design requirements and
limitations of each performance rating. Coordinate
partition performance with specifications for
doors, glazing, penetrations through partitions,
and perimeter construction.
******************************************************************************
1.05 PERFORMANCE
******************************************************************************
UL U427 (One-Hour) requires "H" or "T"
studs at 24 or 30 inches on center. UL U416 (Two-Hour) requires
cavity insulation and an additional layer of gypsum
on furring. Refer to UL publications for additional
requirements.
******************************************************************************
A. Fire Resistance Rating: Test in accordance with
ASTM E119. [Provide where fire-rated
construction is indicated.]
1. Partitions: [One hour-rated; UL U427.] [Two
hour-rated; UL U416.] [________________.]
2. Frames for [Doors] [and] [Glazing]: [20 minute-rated,
WHI classified.]
[____________________________.]
******************************************************************************
42 STC can be obtained with steel "H"-studs
located 24 inches on center. Other studs or spacings may
result in lower ratings. Cavity insulation can be
used to obtain higher ratings. Partitions constructed
according to UL U416 provide 50 STC. See test reports
for additional requirements.
******************************************************************************
B. Sound Transmission Classification: [42] [50]
[________] STC tested in accordance with ASTM E90
by an independent agency and classified in accordance
with ASTM E413. [Provide where sound-
rated construction is indicated.]
C. Structural Performance: Test in accordance with
ASTM E72.
1. Partitions shall withstand a uniformly distributed
load of [5] [________] psf applied
perpendicular to the partition without exceeding
deflection of 1/240 of the partition
height.
2. System shall withstand five 30 ft. lb. impacts
with no observable damage. Instantaneous
deflection shall be one inch max., permanent deflection
set shall be 0.10 inch max.
Test in vertical position.
D. Surface Impact Resistance: Gypsum panels shall
not fracture or break, and no indentation greater
than 1/16 inch measured 24 hours after impact from
an 8 oz., 1-1/2 inch diameter steel ball
dropped from a height of 18 inches; Federal Test
Method Standard No. 406, Method 1074.
******************************************************************************
Where seismic design code requirements govern, consult
USG Interiors representative or qualified
structural engineer for bracing requirements. Include
performance specification here, or provide details
and descriptive specifications as required.
******************************************************************************
E. Seismic Resistance: [________________________________.]
F. Door Slamming: Test shall consist of 1,000 slam
cycles. Door shall be opened 16 inches measured
from lock edge of door to door frame and slammed
shut with a force of 17 ft. lbs. applied
perpendicular to the door opening at door midpoint
vertically and within five inches of lock
edge horizontally. Partition shall pass test if
there is no irreparable damage to frame, door
is fully operable, and fit is as originally installed.
1.06 SUBMITTALS
A. Submit under provisions of Section [01300.] [01340.]
B. Product Data: Submit manufacturer's product
data indicating materials, components, [________],
and standard details to be used. Submit manufacturer's
installation instructions.
******************************************************************************
Shop drawings may not be necessary if required work
can be adequately determined from Drawings,
Specifications and manufacturer's product data.
******************************************************************************
C. Installation Drawings: Indicate [partition layout,]
[panel joint locations,] [connection to
adjacent construction,] [_________________] [and]
special details necessary to supplement or
modify manufacturer's standard drawings and instructions.
D. Samples: Submit [two] [_______] of the following:
1. Complete sets of [swatches] [and] [paint chips]
indicating manufacturer's standard
selection of specified finishes for selection.
******************************************************************************
Retain above if finishes are specified "to be
selected". Retain below to verify specified or selected
finishes.
******************************************************************************
2. Samples 5 x 7 inches with [specified] [selected]
finish[es].
3. Samples 4 inches long of [prefinished metal]
[and] [vinyl] trim showing [specified]
[selected] finishes.
E. Test Data: Submit copies of laboratory tests
indicating requirements for compliance with
performance requirements.
F. Installer Qualifications: Submit letter from
manufacturer indicating acceptability of proposed
installer.
1.07 QUALITY ASSURANCE
******************************************************************************
Contact USG for names of licensed installers in Project
area.
******************************************************************************
A. Installer: Company specializing in relocatable
partition system work and acceptable to
manufacturer.
1.08 MOCKUP
******************************************************************************
Use this Article for large projects where a full
sized erected assembly is required for review of
construction, coordination of work of several Sections,
or testing.
******************************************************************************
A. Provide mockup of partition system under provisions
of Section [01400.] [01405.]
B. [Construct mockup of corner with two [six] [________]
feet long walls [and one "T" intersection].
Include full range of components and accessories
required by project.]
[_________________________________.]
C. Locate mockup [on site] [in installer's shop.]
[_______.]
D. If accepted, mockup will demonstrate minimum
standards for the Work. Mockup may [not] remain as
part of the Work.
1.09 DELIVERY, STORAGE, AND HANDLING
A. Comply with Section [01600.] [01610.]
B. Deliver materials in their original, unopened
packages. Support panels to ensure flatness.
Protect from damage. Remove damaged or deteriorated
materials.
C. Deliver and install after building is enclosed;
permanent heating, cooling, and ventilating
equipment is in operation; and residual moisture
from [plaster,] [concrete,] [________,] [and
other] construction has dissipated. Maintain 65-85
degrees F ambient temperature and 80
percent maximum relative humidity .
1.10 SCHEDULING
******************************************************************************
Retain the following if partitions must be relocatable
without replacing floor or ceiling finishes.
******************************************************************************
A. Install partitions after installation of finished
[floor] [and] [ceiling]. [Install on top of
finished floor.]
1.11 WARRANTY
A. Provide one year manufacturer's limited warranty
under provisions of
Section [01700.] [01740.]
1.12 MAINTENANCE MATERIALS
******************************************************************************
Additional ULTRAWALL components are readily available
from USG Interiors. However, additional materials
can also be stored at designated location if extensive
or frequent remodelling is anticipated.
******************************************************************************
A. Provide additional partition system components
to match installed materials.
1. Wall Components: Provide sufficient components
to construct [_______] linear feet of two-
sided partition. Provide trim for [________] inside
corners, [________] outside
corners, [and] [________] "T" intersections.
2. [Door] [and] [Glazing] Frames: [_________________.]
3. [_________________________________________________.]
B. Furnish items in original packaging clearly labeled
with part number and description. Store in
location designated [on Site.] [________________.]
PART 2 PRODUCTS
2.01 MANUFACTURERS
A. ULTRAWALL Partition System by USG Interiors,
Inc., 101 S. Wacker Drive, Chicago, IL 60606-4385.
******************************************************************************
Partition system substitutions require careful evaluation
of performance, appearance, and coordination
with affected work. Coordinate the following with
Division One and bidding requirements.
******************************************************************************
B. Substitutions: Under provisions of Section [01600.]
[01630.]
1. Submit proposed substitution to Architect in
writing not less than 10 days before bid date.
Acceptance will be by Addendum.
2. Submit product data, samples, proposed installation
details, [test report submittals,]
[and] [________]. Clearly indicate discrepancies
between proposed products and
specified product.
3. Construct full size mock-up showing proposed
components and details.
2.02 FRAMING
A. Struts and Floor Runners: Roll-formed galvanized
steel channel.
B. Ceiling Runners: [Steel] [Aluminum] rails with
internal spacers to maintain position of panels.
******************************************************************************
"H"-STUDS provide the best economy and
fire and sound performance in most applications.
"T"-STUDS allow installation of panels
on one side of partition at a time, providing versatility for
tenant spaces, improved access to utilities in partition
cavity, and staggered installation of panels.
"H/R"-STUDS provide access to cavity while
maintaining separation between partition sides.
ALUMINUM STUDS for wall mounted furniture systems
are also available. Contact USG Interiors for
additional information.
******************************************************************************
C. Studs: Roll-formed galvanized steel; [.021 inch
minimum uncoated steel thickness for partitions
up to 9'-6" high] [and] [.027 inch minimum uncoated
steel thickness for partitions over 9'-6"
high].
1. "H"-Studs: [Provide at all locations
except where another type is required.] [Provide at
[fire-rated] [and] [sound-rated] walls.]
2. "T"-Studs: Provide where [one-sided
construction] [or] [staggered gypsum panels] are
required [and where shown on Drawings].
3. "H/R"-Studs: Provide where removable
panels for access to partition cavity are required
[and where shown on Drawings].
******************************************************************************
Furring is required for two-hour fire resistance
rating.
******************************************************************************
D. Wall Furring: Roll-formed galvanized steel;
.021 inch minimum uncoated steel thickness.
2.03 PANELS
******************************************************************************
Maximum panel height is ten feet.
******************************************************************************
A. Gypsum Panels: 3/4 inch thick x [24] [30] inches
wide x height of partition; edges beveled and
kerfed for installation on studs, square cut ends;
comply with ASTM C36.
2.04 DOORS AND GLAZING
******************************************************************************
Select door frame type desired.
******************************************************************************
B. Door Frames:
1. Aluminum: SMR Delta Door Frames; self mortising
and reversible.
2 Steel:
a. DONN Steel Door Frames; throated type, capable
of installation without regard to panel
module, non-handed and reversible, and formed of
galvanized steel.
a. [At fire-rated partitions, provide one hour-rated
[and WHI labelled] Class B frames.]
c. Door Slamming: Frame shall withstand one million
slam cycles.
In each cycle, door shall be opened 16 inches
and slammed shut with a force of 17 ft.
lbs. applied perpendicular to the door opening at
door midpoint vertically and
within five inches of lock edge horizontally. There
shall be no irreparable
damage to frame and door shall fit as originally
installed and remain operable.
3. Hollow Metal Frames: Specified in Section [08100.]
[________.]
******************************************************************************
Hardware should usually be specified in Division
8, but can be added to this Section if appropriate.
Standard hardware preparation for ULTRAWALL door
frames is for 1-1/2 pair of 4-1/2 x 4-1/2 inch mortised
butt hinges (2 pair for full-height doors) and a
4-7/8 x 1-1/4 inch strike per ANSI A115.1 and 115.2.
******************************************************************************
C. Hardware: [Prepare frame for hardware specified
in Section [08700.] [________.]] [Provide
[________________________.]]
******************************************************************************
Doors should usually be specified in Division 8,
but can be added to this Section if appropriate.
ULTRAWALL frames are sized for 1-3/4 inch thick doors.
Specify fire resistance-rated doors and frames in
fire resistance- rated partitions.
******************************************************************************
D. Doors: [As specified in Section [08100.] [08200.]
[________.]] [__________________________.]
E. Window Frames: [Match specified trim group.]
[________________.] Provide resilient glazing
gaskets.
******************************************************************************
Glass should usually be specified in Division 8,
but can be added to this Section if appropriate.
Specify glass and glazing with regard to fire- resistance,
sound transmission coefficient, and safety
glazing requirements.
******************************************************************************
F. Glass: [[_________________] type[.] [specified
in Section 08800.]]
[_______________________________.]
2.05 TRIM AND ACCESSORIES
******************************************************************************
Specify steel and vinyl trim for economy, aluminum
trim when required for appearance.
******************************************************************************
A. Trim: [Steel and vinyl.] [Extruded aluminum.]
B. Base: [Vinyl base attached with base clips.]
[Specified Section [09650.] [09680.] [________.]]
******************************************************************************
Coordinate insulation with fire resistance rating
and sound transmission classification.
******************************************************************************
C. Insulation: THERMAFIBER Sound Attenuation Fire
Blankets, paperless, semi-rigid mineral fiber
mat, [[1 inch] [1-1/2 inches] thick] [thickness required
to provide specified performance], cut
to fit stud spacing; FS HH-I-521.
D. Acoustical Gaskets and Sealant: Compressible
foam gaskets and USG Acoustical Sealant.
E. Fasteners:
1. Floor Runner to Floor: [Type recommended by
system manufacturer.] [Carpet gripper.]
[Double-stick foam tape.] [Screws or anchors.] [________.]
2. Ceiling Runner to Ceiling: [Type recommended
by system manufacturer.] [________.]
3. Gypsum Panels to Struts and Floor Runners:
1-1/4 inch type S bugle head screw.
4. Other Conditions: Fasteners and adhesives recommended
by system manufacturer.
F. Posts: Extruded aluminum, [____ x ____] inches.
G. Provide other materials [as required to achieve
specified levels of performance and] in
accordance with system manufacturer's instructions.
2.06 FACTORY FINISHES
******************************************************************************
Select required finishes. Vinyl wall coverings are
available from USG Interiors in matching colors for
field applied finishes. Refer to current catalog
or swatch book for additional information.
******************************************************************************
A. Vinyl Covered Gypsum Panels: Comply with ASTM
C960.
1. Color and Pattern: [[________] color, [________]
pattern, [________] average light
reflectance.] [Color and pattern as selected from
manufacturer's standards.] Within
each wall area, vinyl shall be from the same product
lot and pattern shall be installed
in same direction to minimize variation in color
or appearance.
2. Surface Burning Characteristics: Maximum [________]
flame spread and [________] smoke
developed; ASTM E84.
******************************************************************************
Following applies to materials which are fabric
backed.
******************************************************************************
3. Comply with FS CC-W-408A, Type I (Light Duty).
B. Fabric Covered Gypsum Panels: [[________] color,
[________] pattern.] [Color and pattern as
selected from manufacturer's standards.] Within
each wall area, fabric shall be from the same
product lot and pattern
shall be installed in same direction to minimize
variation in color or appearance.
1. TEK-WALL 1000: Woven, solution-dyed polyolefin
fibers, 22.0 oz.
2. Donegal Tweeds: Woven polyester and polyester/wool,
19.0 oz.
3. Wovens: Woven polyester and polyester/wool,
16.5 oz.
C. Unfinished Panels: Paper faces for field finishing.
D. Custom Finished Panels: [____________________________.]
E. Aluminum Surfaces: [Dark bronze color-anodized
to AA C22-A32.] [Clear anodized to AA C22-A21
satin finish.] [Painted [________] color[.] [selected
from manufacturer's standards.]]
F. Steel Surfaces: [Shop applied baked enamel of
[______] color[.] [selected from manufacturer's
standards.]]
G. Vinyl Trim Surfaces: Color selected from manufacturer's
standards.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that building conditions are ready to
receive partitions. Take floor-to-ceiling
measurements to ensure correct installation of full-
height frames.
B. Beginning of installation means acceptance of
existing conditions.
3.02 INSTALLATION
A. Install in accordance with manufacturer's instructions[.]
[and in accordance with approved
designs for performance-rated partitions.]
B. Install rigid, plumb, with horizontal lines leveled,
neat in appearance, and free from defects.
******************************************************************************
Partitions are usually installed to finished ceiling.
Install to structure above if required for fire or
sound control or security.
******************************************************************************
C. Extend partitions from floor to [finished ceiling]
[structure above] [[________] inches above
floor] [except where otherwise indicated].
******************************************************************************
Retain below if partition is installed after floor
or ceiling finishes are installed. Note that certain
fire-rated designs require anchor-bolts which may
mar floor or ceiling finishes.
******************************************************************************
D. [Secure partitions to [floor] [and] [ceiling]
using fastening devices which will not excessively
mar finished surfaces.]
E. Use concealed fasteners except where otherwise
shown in manufacturer's product data or required
by conditions.
F. Coordinate installation of [mechanical,] [electrical,]
[and other] work placed on or within
partition.
G. Layout partition centerlines [on ceiling [for
ceiling height partitions]] [and] [on floor [for
partial height partitions]]. Install ceiling runner,
then floor runner. Check for plumbness
before fastening floor runner. Install strut studs
at door openings and wall terminations.
H. Panels: Install vertically with butt panel joints.
[Space as shown on layout drawings.] [Space
to minimize use of cut panels.] [To extent practical,
space panels symmetrically on each wall;
layout to avoid use of panels less than half width
of full panel.]
I. H/R Studs: Install with access panels [as shown
on Drawings.] [on alternating sides of
partitions to allow access to each partition cavity
while maintaining separation of areas on
opposite sides of partitions.] Mark location of access
panels with a permanent red "X" located
beneath base trim.
H. Bracing: Provide concealed supports if required
to assure lateral stability of partitions.
[Install posts from floor to ceiling at ends of partial
height partitions.] [Provide
additional bracing or blocking where required to
support partition mounted fixtures.]
J. Partition Insulation: [Provide in [fire-rated]
[and] [sound-rated] partitions.] Install tight
within spaces, around openings, behind and around
electrical and mechanical items within
partitions, and tight to items passing through partitions.
Staple or adhere to back side of
panels.
K. Acoustical Gaskets and Sealant: Seal cut-outs
in panels, penetrations through partitions, and
intersections with adjacent construction. Use gaskets
where practical; use sealant at other
locations[.] [and in fire rated partitions.]
L. Vapor Retarder: [________________________.]
M. Doors and Hardware: Install as specified in
Section [________]. Adjust for proper operation.
3.03 CLEANING AND PROTECTION.
A. Clean partitions.
B. Protect against damage. Repair or replace damaged
components.
3.04 SCHEDULE
******************************************************************************
When required, several types of ULTRAWALL partitions
can be used to satisfy conditions which may occur at
different locations on Project. If locations of
different types of partitions are not shown on Drawings,
include schedule as shown in following example.
******************************************************************************
A. Partitions Adjacent to Corridor No. 118: Fire-rated;
extend to underside of structure; fabric
finish; "H"-Studs.
B. Partitions in General Office No. 250: 7'-0"
cornice height; vinyl finish; "H"-Studs.
C. Other Partitions: Sound-rated; install from floor
to ceiling; fabric finish; "T"-Studs.
END OF SECTION
TRADEMARKS: The following trademarks used herein
are owned by USG Interiors, Inc.: THERMAFIBER,
ULTRAWALL, USG.
Copyright 1990 by USG Interiors, Inc. A limited
license is extended to qualified design professionals to
copy this guide specification for the purpose of
incorporating products manufactured by USG Interiors
into a construction specification or purchase order.
ULTRAWALL10615 - GUIDE SPECIFICATION